V 20-C/...: Surge protection device Type 2 (Class C) to VDE 0675 part 6-11 (DIN EN 61643-11) with acoustic signalling.
• Complete unit consisting of upper part and base, pre-mounted and ready for connection
• With acoustic signalling for function monitoring, signal tone can be shut down for 24 h
• VDE-tested
• Suitable for TN and TT network systems
• Plug-in upper part; upper part can be separated from base without tools
• Including thermal and dynamic separating device
• With visual display of defects
• High current conductivity and long service life
V20-C 3+NPE+AS | ||||||||||||||||||||||||||
Nominal voltage | UN | 230 | ||||||||||||||||||||||||
SPD to EN 61643-11 |
| Type 2 | ||||||||||||||||||||||||
SPD to IEC 61643-11 |
| Class II | ||||||||||||||||||||||||
Lightning protection zone LPZ |
| 1→2 | ||||||||||||||||||||||||
Nominal discharge current (8/20) | In | 20 | ||||||||||||||||||||||||
Arrestor surge current (8/20) [total] | ITotal 8/20 | 80 | ||||||||||||||||||||||||
Maximum discharge current (8/20 μs) | Imax | 40 | ||||||||||||||||||||||||
Voltage protection level | Up |
| ||||||||||||||||||||||||
Response time | tA |
| ||||||||||||||||||||||||
Maximum back-up fuse |
| 125 | ||||||||||||||||||||||||
Temperature range | ϑ | -40-80 | ||||||||||||||||||||||||
Division unit TE (17.5 mm) |
| 5 | ||||||||||||||||||||||||
Protection rating |
| IP20 | ||||||||||||||||||||||||
Connection cross-section rigid |
| 2,5-35 | ||||||||||||||||||||||||
Connection cross-section, multi-wire |
| 2,5-35 | ||||||||||||||||||||||||
Connection cross-section, flexible |
| 2,5-25
|