面议I General
HD106 Conventional Beam Detector (hereinafter called the detector) is a nonaddressable
infrared beam smoke detector, which must be used together with a
reflector. The number of reflector(s) to be used (one or four) depends on the
distance from the detector.
With excellent built-in microprocessor, the detector has strong ability of analysis and
judgment. The detector can automatically carry out system adjustment, compensation
of variation of ambient data, and judgment of fire and fault through fixed algorithm, and
indicate these states by LED and signal output terminals. With new and reasonable
design, attractive appearance, flexible adjustment and alignment method it’s easy to
install and adjust. The sensitivity of the detector can be set through hand held
programmer in field, decreasing the demand for cleanliness of field
conditions, and enlarging application areas. The detector is applicable
to historical buildings, warehouses, large storages, shopping malls, leisure
centers, exhibition halls, hotel lobbies, printing houses, clothing factories,
museums and prisons etc, as well as places where slight smoke particles exist.
II Features
(1) Wide operating voltage range, big monitoring areas.
(2) Combination of the emitting and receiving part makes mounting easy and optical
pathway accurate.
(3) Built-in microprocessor enables intelligent judgment of fire alarm and fault.
(4) The detector can calibrate automatically, which ensures that one person complete
adjustment in short time. It’s also convenient to operate.
(5) Self-diagnosis function can monitor the inner fault.
(6) Automatic compensation for factors weakening received signals, such as dust
contamination, positional excursion and ageing transmitter.
(7) It has passive output contacts for fire alarm and fault.
(8) Two sensitivity levels can be set in field.
(9) The detector’s optical pathway is designed with strong anti-interference ability.
(10) SMT processing technology.
(11) Attractive and decent appearance.
III Technical Specifications
(1) Power Voltage: 15VDC to 28VDC
(2) Power Current: Commission current›20mA
Standby current›12mA Alarm
current›22mA
(3) Fire Alarm and Fault Contact Output:
Fire Alarm Relay: Contact capacity 28V/2A, which is normally open in normal state
Page 1
HD106
Conventional Beam Detector
Installation and Operation Manual
and closed in fire alarm state.
Fault Relay: Contact capacity 28V/2A, which is normally open in normal state and
closed in fault state.
(4) Angle of Adjusting: -6° to +6°
(5) Sensitivity Level:
Level 1: High sensitivity.
Level 2: Medium sensitivity.
(6) Indication of Detector State:
Commission: Green LED and Yellow LED are lit or flash in a certain way. See
details in Section VI Commission.
Normal monitoring state: Red LED flashes periodically.
Fire: Red LED constantly illuminates, and Yellow LED turns off. Fire alarm should
be cleared through powering up again.
Fault: Yellow LED constantly illuminates. The detector clears the fault
signal automatically if the condition causing the fault disappears.
Optical pathway obscured totally: the detector first gives fault signal and turns
on Yellow LED. 20s later, it alarms fire, illuminates Red LED and turns off Yellow
LED. Note: In this case, it does not mean there is a fire. After the obscuration
is removed, the detector clears fault signal automatically. Fire signal has to
be cleared by powering up the detector again.
(7) Operating Environment:
Temperature: -10°C to +50°C
Relative Humidity: 95%, non condensing
(8) Monitoring Area: Maximum monitoring area: 1400m2
Maximum width: 14m
(9) Length of Optical Pathway: 8m to 100m
(10) Protection Level:
Under common environment, ingress protection rating is IP20.
Under special environment, ingress protection rating is IP66 through
glue-seal treatment.
(11) Dimension: length: 206mm width: 95mm thickness: 95mm
(12) Material and Color of Enclosure: ABS, gray
(13) Weight: 450g
(14) Mounting Hole Spacing: Spacing for embedding: 158mm
Spacings for surface mounting: 79mm to 96mm