品牌
经销商厂商性质
武汉市所在地
南澳电气NATRQ钳形接地电阻测试仪是南澳电气公司研发团队对技术品质的追求,通过不断创新完善,对老款产品的*升级。广泛应用于电力、电信、气象、油田、建筑及工业电气设备等的接地电阻测量、回路电阻测量。在测量有回路的接地系统时,不需断开接地引下线,不需辅助电极,安全快速。能测量出用传统方法无法测量的接地故障,能应用于传统方法无法测量的场合,因为测量的是接地体电阻和接地引线电阻的综合值。
有长钳口及圆钳口之分,长钳口特别适宜于扁钢接地的场合。NATRQ钳形接地电阻测试仪还能测量接地系统的泄漏电流和中性线电流。
南澳电气NATRQ钳形接地电阻测试仪产品别名
单钳口接地电阻测试仪,钳形接地电阻测试仪,钳型接地电阻仪,钳型接地电阻表,钳形接地电阻仪,钳形接地电阻表,接地电阻,接地表,地阻仪,接地电阻仪,接地电阻测量仪,钳式数字接地电阻测试仪,钳式接地电阻测试仪
南澳电气NATRQ钳形接地电阻测试仪产品特性
1、N南澳电气NATRQ钳形接地电阻测试仪适用于各种形状的接地引线(园钢、扁钢及角钢)
2、非接触式测量接地电阻、安全、快速
3、不必使用辅助接地棒,不须中断待测设备之接地
4、NATRQ钳形接地电阻测试仪具有双重保护绝缘
5、抗干扰性强,测量精确度高
6、使用5号碱性电池方便用户
Product introduction
NATRQ Clamp-On Ground Resistance Tester is a major technological breakthrough in traditional grounding resistance measurement. It is widely used in the grounding resistance measurement of electric power, ecommunications, meteorology, oilfield, construction and the industrial and electrical equipment.
NATRQ series Ground Clamp Meter, in the measurement of a grounding system with loop current, does not require disconnecting the grounding wire, and need no auxiliary electrode. It is safe, fast and simple to use.
NATRQ series Ground Clamp Meter can measure out the faults beyond the reach of the traditional methods, and can be applied in the occasions not in the range of the traditional methods. NATRQ series Earth Ground Clamp Meter can measure the integrated value of the grounding body resistance and the grounding lead resistance.
NATRQ series Ground Clamp Meter are equipped with either a long clamp or a round clamp, as indicated in the figure below. A long clamp is particularly suitable for the occasion of grounding with the flat steel.
In addition, NATRQC Earth Ground Clamp Meter is also able to measure the leakage current and the neutral current in the grounding system.
Also called name
Ground resistance tester, ground clamp meter, ground clamp resistance tester
The Characteristics of the products
1. Applies to all kinds of ground lead. (round bar, flat bar, angle iron)
2. non-contact measured resistance, safe ,fast.
3. need not use assistant ground rod.
4. with double protecting insulation.
5. with strong anti-interference ability and high accuracy.
6. use dry batteries, convenient use for customers.
NASJX Multifunction Dual-Clamp Earth Resistance Tester NASJX双钳接地电阻测试仪
产品简介
优良的接地系统是电力、电信、电气设备安全可靠运行的重要保证。接地电阻大小是接地系统品质优劣的评判依据。精确、快速、简捷、可靠的接地电阻测量方法,已成为防雷接地领域内技术进步的迫切需要。NASJX双钳接地电阻测试仪适用于电信、电力、气象、机房、电力配电线路、铁塔输电线路、加油站、工厂接地网、避雷针等。
NASJX双钳接地电阻测试仪除了具有传统打辅助地极测接地电阻的功能外,还具备了无辅助地极测量的*功能,改变了测试接地电阻传统的测量原理和手段:采用双钳口非接触测量技术无需打辅助地极,也无需将接地体与负载隔离,实现了在线测量。在单点接地系统、干扰性强等条件下,可以采用打辅助地极的测量方式进行测量。
产品别名
双钳接地电阻测试仪,多功能双钳接地电阻测试仪,多功能接地电阻测试仪,双钳口接地电阻测试仪,钳形接地电阻测试仪,接地电阻,接地表,地阻仪,接地电阻仪,接地电阻测量仪,数字式接地电阻测试仪,数字接地电阻测试仪,双钳式接地电阻测试仪,钳式数字接地电阻测试仪,双钳数字接地电阻测试仪,钳式接地电阻测试仪
产品特性
1.双钳法/地桩法双重测量方式:
适合任意接地场所,多点或单点接地,都可正常测试;
2.抗*力强:
自产生高频电流,从而过滤市电中50Hz、100Hz等谐波干扰电流,即使在500KV变电站环境下,也能精确测量;
3.测量范围广、分辨率高:
量程从0.01Ω~200Ω,分辨率0.01Ω,对0.7Ω以下接地电阻,也能准确测量;
4.大钳口设计:
钳口直径50mm(标准配置),满足用扁铁/钢作接地引线的情况,特殊钳口尺寸可按客户要求定制;
5.大容量数据存储:可储存200组测量数据;
6.操作简单,单人作业:
中英文操作界面、体积小、重量轻,防爆便携箱,野外测量携带方便。
产品参数
接地电阻测量范围 | 双钳法 | 0.01Ω~200Ω |
地桩法 | ||
准 确 度 | 双钳法 | ±3%±2个字 |
地桩法 | ±2%±2个字 | |
zui小分辨率 | 0.01Ω | |
钳口尺寸 | Φ50mm | |
存储容量 | 200组数据 | |
工作温度 | 0℃~ + 50℃ | |
供电方式 | 8节5号镍氢充电电池或普通AA电池 | |
重 量 | 0.8KG(含电池) | |
尺 寸 | 265mm×130mm×65mm |
Product introduction
Excellent grounding system is very improtant to ensure the power, ecommunications, electrical equipment safe and reliable operation. Grounding resistance grounding system size is based on the quality of the merits of the judgment. Accurate, fast, simple and reliable grounding resistance measurement method, the area has become a lightning protection and grounding technological advances are urgently needed. NASJX double clamp earth resistance tester for ecommunications, electricity, weather, room, power distribution lines, tower transmission lines, gas stations, factories grounding, lightning and so on.
NASJX has traditional fight auxiliary earth ground resistance measurement functions, also has no auxiliary measuring the unique features of the earth, changing the traditional testing ground resistance measurement principle and means: Double clamp mouth non-contact measurement technology eliminates the need to fight auxiliary earth, and without the grounding body and load isolation, to achieve an online survey. In the single-point grounding system, strong interference and other conditions, can be used to fight the auxiliary earth electrode measurement measurement.
Also called name
Earth resistance tester, dual-clamp resistance tester,Double Clamp Ground Resistance Tester, multifunction double clamp earth resistance tester, multi-ground resistance tester, double jaw Ground Resistance Tester, Clamp Ground Resistance Tester, Ground Resistance, Ground sheet, ground resistance meter, earth resistance meter, earth resistance meter, digital ground resistance tester, digital ground resistance tester, dual clamp ground Resistance Tester, digital ground Resistance Tester clamp, double Clamp digital ground Resistance Tester, clamp-on ground Resistance Tester
The Characteristics of the products
1. Dual clamp/ ground anchor two methods:
applies any ground site, single or multiple point grounding.
2. Strong anti-jamming ability
3. Wide measurement range, high resolution
range: 0.01Ω~200Ω, resolution: 0.01Ω,
4. Big jaw design:
diameter :50mm (standard), special size according customers’ requirements.
5. Large-capacity data storage:200 groups
6. Easy to operate:
small in volume, light in weight, portable explosion proof case, convenient to field test to carry.
The parameters of the products
1. Earth resistance measurement range:
dual clamp: 0.01Ω~200Ω
ground anchor: 0.01Ω~200Ω
2. Error:
dual clamp: ±3%±2 d
ground anchor: ±2%±2 d
3. Minimum resolution: 0.01Ω
4. Jaw size: Φ50mm
5. Storage Capacity: 200 groups
6. Temperature: 0℃ ~ + 50℃
7. Power supply: eight Ni-MH rechargeable batteries or common AA battery
8. Weight: 0.8KG (includes the battery)
9. Dimension: 265mmx130mmx65mm
Product information
1, jaw and host as a whole set. To avoid measurement errors, do not use the jaw of NASJX Double Clamp Ground Resistance Tester hosts for other host.
2, must keep iron core contact surfaces of the jaw clean, or else contaminated instrument jaw will reduce measurement accuracy.
3, keep the jaws closed well during the test to avoid stuck phenomenon.