扬州市昂立电气有限公司

智慧城市网中级12

收藏

滑触线电源进线与信号灯的安装

时间:2016-01-03      阅读:2103

1、电源进线与信号灯的安装。用一根40mmx4mm的镀锌扁钢弯制而成的。弯制的扁钢焊在滑触线上,焊接前应先钻好孔,在孔周围搪好锡以使接线端子与扁钢的接触良好。
1, the power supply into line with the installation of lights. With a 40 mmx4mm galvanized flat steel bending. Bending of the flat steel welded on the sliding contact line, should be good drill hole before welding, around the hole boring good tin to make terminal blocks have a good contact with the flat.
2、当滑触线长度超过50m时,为适应温度变化而引起滑触线的伸缩,也应装设补偿装置。
2, when the sliding contact line length of more than 50 m, in order to adapt to the temperature change caused by the expansion of sliding contact line, should also be installed compensation device.
当滑触线的线路较长,电压降超过允许值时,滑触线上应加装辅助铝母排,每隔12m用M10螺栓螺母连接一次,连接处应搪锡。
When the line of the sliding contact line is longer, the voltage drop exceeds allowable values, sliding contact line should be equipped with auxiliary aluminum busbar, every 12 m with M10 bolt and nut connection time, technicians to joint should be tin.
3、滑触线跨越建筑物伸缩缝时,滑触线应装有膨胀补偿措施。滑触线在伸缩缝的间隙,一般为10-20mm。间隙两侧的滑触线端头应加工圆滑,接触面安装在一水平面上,其两端高差不能大于1mm。在靠近伸缩缝的两侧滑触线应加装支架,从间隙中心线到支架中心线的距离不应超过150mm。

 

3, sliding contact line across the building expansion joints, sliding contact line is supposed to contain inflation compensation measures. Sliding contact line on the expansion joint clearance, generally for 10 to 20 mm. Clearance on both sides of the sliding contact line end should be processing, smooth interface is installed in a horizontal plane, the elevation difference is not greater than 1 mm at both ends. Near the expansion joint of two side sliding contact line should be equipped with stents, the distance from the center line of the clearance to support the centerline should not exceed 150 mm.

上一篇: TGSG系列报警器规格型号 下一篇: 液压千斤顶操作注意事项
提示

请选择您要拨打的电话: